Home: EcoVantage Catalog: Batteries: Large:
GNB Absolyte® XL Cat. No. GNB-AXL Weight 695 lbs | |
The Most Reliable
Post and Jar to Cover Seal
Design State of the Art Design
As an industrial battery ages, chemical corrosion causes the positive
plates to expand, placing pressure on the posts, the cover and the
seals. Excessive plate growth, which can be caused by high temperature
environments, will cause the positive plate to damage the cover and
seals, thus shortening the life of the battery. The XL design
eliminates this failure mode by removing stresses placed on the
seals and cover by forcing the growth away from the seal.
- The steel face plate eliminates stress
on cover, and improves heat dissipation through cover
- The post restraint spacer eliminates stress on post using the
face plate for support.
- Plate growth is forced away from the posts and cover seals.
- Additional space to accommodate the positive plate growth.
- Horizontal plate stacking improves heat dissipation through tray.
- High separator compression within the cell maintains plate to
separator contact, preventing capacity loss.
- Unique “S” wrap absorbed glass mat separator design prevents
positive (orange) plate to negative (gray) plate shorting.
- The XL post seal design eliminates the lead to lead bond with a
completely non-corrosive polypropylene to polypropylene bond – formed
by a fusion process that creates a bond as strong as, or stronger than
the original material.
- The interface between the lead post and the plastic sleeve is
coated with a viscous bonding agent which guarantees a leak free bond.
- The proven tongue and groove seal technology used on the jar to
cover seal improves seal strength and durability.
The Most Reliable Post and Jar to Cover Seal Design
| Absolyte®
XL Quick Specs |
| System Ampere-hour Range: |
2000 to 6000 Ah to 1.75 VPC at 8
hour rate |
| Container and Cover. |
Flame Retardant Polypropylene
standard (UL94 V-0/28% L.O. |
Positive Plate:
|
MFX grid alloy (patented) |
Negative Plate:
|
Lead Calcium grid alloy |
Separator:
|
Absorbent glass mat (AGM) |
Electrolyte:
|
1.295 Specific Gravity Acid |
Terminals:
|
Solid Copper |
Safety Vent:
|
5-10 psi opening pressure, self
resealing |
Container to Cover Seal:
|
Polypropylene to polypropylene
fusion bond |
Post to Cover Seal:
|
Polypropylene to polypropylene
fusion bond |
Float Voltage:
|
2.23 to 2.25 VPC |
Life Expectancy in Float
Conditions:
|
20 years at 25°C(77°F)
and following proper charging conditions |
Life Expectancy in Cycling
Conditions:
|
1200 cycles to 80% DOD |
| Operating Temperature: |
Temperature excursions
between -40°C (-40°F) to
+50°C (122°F) allowed (Battery performance and life will be
affected) |
| Seismic Zone
4 Certified: |
|
| 1994
UBC (At all levels) |
1997
UBC (At or below grade) |
XL2000: 6 high
XL3000: 4 high |
XL2000: 6 high
XL3000: 6 high |
MODULE TYPE
|
VOLTS** |
NOM
AH CAP
(8 HR) |
STACKING DIMENSIONS |
MAXIMUM
UNPACKED WEIGHT |
| LENGTH |
DEPTH* |
HEIGHT |
IN
|
MM
|
IN
|
MM |
IN |
MM |
LBS
|
KG
|
XL2000
|
4
|
2000
|
38.09
|
967
|
21.36
|
543
|
11.46
|
291
|
695
|
315
|
XL3000
|
4
|
3000
|
38.09
|
967 |
21.36 |
543 |
15.57
|
396
|
985
|
447
|
| XL4000 |
4 |
4000 |
38.09 |
967 |
21.36 |
543 |
22.91 |
583 |
1,389.2 |
630 |
| XL5000 |
4 |
5000 |
38.09 |
967 |
21.36 |
543 |
27.05 |
687 |
1,680.2 |
762 |
| XL6000 |
4 |
6000 |
38.09 |
967 |
21.36 |
543 |
31.18 |
792 |
1,971.3 |
894 |
*
Includes 80 mm (3.15") additional for Module Cover Assembly
** 2 Cells Per Module
Note: Design and/or specifications subject to change without notice. If
questions arise, contact your local GNB sales representative for
clarification. |
Horizontal Stack Assembly
• Depth is overall, including module cover assembly.
• Add 102mm (4") for bottom I-beam supports to determine the total
height of each assembled horizontal stack.
• Allow 152mm (6") additional clearance wherever a terminal plate