Basic Operation
This Genset starter monitors the battery voltage, and when the
battery voltage gets too its low setpoint, the unit starts the
generator. When the battery gets to its high setpoint, the unit stops
the generator. The generator may be remotely started and stopped by dry
contact closures,
or by its local toggle switch start stop commands. The setpoints may be
temperature compensated with an optional remote temperature sensor.
Available in Model (GS-1AC) optimized for starting AC generators or
Model (GS-1DC) for DC generators.
This product is available in an enclosure or open frame design for
mount in your own enclosure.
Features
- Single unit 12 V up to 48 V battery systems
- LEDs indicate relay positions and generator status
- Temperature compensation (-4 mv / deg C./ cell) on start and stop
voltages with optional temperature sensor TC-2
- remote start and stop controls as well as local start/stop
control
- 5 second retirggerable time delay on voltage sensing to prevent
false starts/stops
- Supports 2, 3 and 4 wire systems as well as advanced control
systems
- Low Cost/ High Reliability
Electrical Specifications
- Base Model: GS-1
- Nominal battery voltages 12 - 48 V DC
- Maximum Input (V) 63
- Minimum Voltage 10
- Relay: 8 amps @ 12/24 V , 2 amp @ 48 V , 5 amps @ 120 VAC rating
of Potter and Brumfield T72 series relay
- Self Consumption (A)
-
- Relay Power: 0.5W per relay coil when powered, voltage
independent
-
- Quiescent less than 20 mA,Fusing 1 A, internal
electronics only
Sequence of Operation on Startup
When the battery voltage is detected as too low per user adjustable
setpoint the generator goes through its start sequence.
- The Generator start LED comes on.
- Precrank: 20 seconds relay closure (with LED on) prior to
generator start/crank.
- Crank:
relay closure (with LED on) for 10 seconds or until Genset start
detected defined by generator/battery voltage starting to rise.
- Run: Relay closure (with LED on) whenever generator is cranking
or running.
- Load: load relay closure (with LED on) for 30 seconds after run
relay closure.
- If battery voltage falls another 0.2 V (relative to 12 V
battery), fault relay is activated for remote signaling of fault.
Sequence of Operation on Shutdown
When the battery has charged to the user adjustable setpoint, the
generator goes through its stop sequence.
- The Generator Stop LED comes on, start light turns off.
- Load: Load Relay opens (with LED off).
- Run: Run relay opens (with LED off) 20 seconds after load relay
opens.
- Stop: Stop relay Closes (with LED on) for 10 seconds after run
relay opens.
User Controls
- Generator Stop Voltage
- Generator Start Voltage
- Manual start/stop toggle switch overrides remote smart stop
control
- Remote start/stop
- Potentiometers
and test points read 1/10 the voltage you wish to start/stop the
generator. For example, if the generator is required to start at 23 V,
set the start potentiometer for 2.3 V
LED Display
- Generator start/stop
- Relay position for precrank, crank, load, run, stop, fault
Mechanical Specifications
Weight:
- GS-1 weighs 0.5 lbs. open frame
- GS-2 weighs 8 lbs. NEMA 3R box
Size:
- GS-1 measures 5" X 5" X 1" open frame
- GS-2 measures 10" X 8" X 4" NEMA 3R box
Connections:
- Power:
Euro-style Terminal Strip # 12 AWG
Operating Temperature:
Humidity:
Note: In the interest of continuous product improvement
specifications subject to change without notice.
Order Model No:
AC Model: Controls Gensets that have an AC generator powering a battery
charger connected to the battery.
- GS-1AC open frame for mount in user system
- GS-2AC with NEMA 3R enclosure
DC Model: Controls Gensets that have a DC output directly to the
battery.
- GS-1DC open frame for mount in user system
- GS-2DC with NEMA 3R enclosure